KMC Controls REE-5002 User Manual

Installation guide, Mounting, Connections and wiring

Advertising
background image

Installation Guide

Triac Relay Module, Fan with 2-Stage Reheat

REE-5002

Mounting

Connect as shown below and/or in the sample

illustration on the next page. Supply the relay with

24 VAC, +20%/ –15%. (Use wire size of 14 to 22 AWG,

stranded.)
NOTE: Triac outputs

are for 24 VAC loads only.

Check the graph for thermostat signal setpoints and

corresponding stages. Stage 2 turns on at 1 VDC,

Stage 1 at 3 VDC, and the Fan at an adjustable level

beteen 3 and 8 VDC.
To adjust the Fan start point, connect a voltmeter

between the X and — terminals and then adjust the

potentiometer accordingly.

The

REE-5002 may be mounted directly to a control

box surface or in a 2 x 4" electrical handy box. Add a

blank cover to conceal the module if desired.

Mounting

1

Connections and Wiring 1
Troubleshooting 2
Maintenance

2

REE-5002

Installation Guide

Connections and Wiring

NOTE: There is a 1 VDC switching differential on

each stage.

Advertising
Table of contents