CTE-3016/3017/3026/3027

1

Installation Guide

Installation Guide

Low Limit Controllers, DPDT

CTE-3016/3017/3026/3027

Mounting

1

Wiring

1

Actuation and Reset 2
Setpoint Adjustment 2
Testing

2

Accessories

2

Maintenance

2

Specifications 2
Important Notices 2

Mounting

The controller can be mounted in any position,

but avoid locations subject to excessive vibration.

For manual reset models, position the controller to

permit convenient access to the reset button.
1. Loosen the front screw and remove the cover.
2. Using the two 3/8" mounting keyholes, mount

the case flush against the duct work or any flat

surface.

3. Install the sensing capillary in a horizontal

serpentine fashion across the downstream side of

a water coil.

4. Using the included HMO-4523 capillary clips,

support the sensing capillary at sufficient points

to prevent damage from vibration and/or air

movement.

CAUTION

Do not kink or apply excessive force to the capillary
element.

5. Make the appropriate connections to the terminal

blocks. (See the Wiring section.)

Wiring

An opening for installing a connector for 1/2" conduit

is provided in the bottom of the case.
All wiring should comply with national and local

electrical codes. Using 14 AWG solid copper wire is

recommended.
Strip wire ends 3/8", insert the wire ends under

the cup washers on the switch block, and securely

retighten terminal screws. Wire terminals according

to the Actuation and Reset section on the next page.

CTE-3017 Shown