KMC Controls REE-5123 User Manual

Installation guide, Mounting connections and wiring

Advertising
background image

REE-5106/5123

1

Installation Guide

Installation Guide

Relay Module, Proportional Reheat w/ Thermostat Power Supply

REE-5106/5123

Mounting 1
Connections and Wiring 1
Troubleshooting 2
Maintenance 2
Important Notices 2
More Information 2

The

module may be mounted directly to a control

box surface or in a 2 x 4" electrical handy box. Add a

blank cover to conceal the module if desired.

Mounting

Connections and Wiring

Wire as shown for providing proportional reheat to

an electric hot water valve. Supply the relay with 24

VAC (+20%/–15%) from a Class 2 transformer. (Use

wire size of 14 to 22 AWG, stranded.)

All dimension are in inches (mm)

Valve

Closed

Valve

Open

Room Temperature

10

2 VDC

Thermostat

Signal (RA)

Water

Flow

NOTE: The REE-5123 (shown on the next page) has

been discontinued.

NOTE: For REE-5106 use with a CTE-5202

thermostat, see the

CTE-5202 Applications

Guide

on the KMC web site.

REE-5106

Advertising
This manual is related to the following products: