Installation Guide

Manual Reset High Limit

CTE-6001

Wiring

Mounting

1.

Drill an opening in the supply air duct to accept

the 3/4" diameter sensor.

2. Mount the unit on the duct using three self-

tapping screws in the 7/32" diameter mounting

holes.

1. Thread wiring for the low-voltage or line-voltage

circuit through the two 7/8" knockouts.

NOTE: If more than one CTE-6001 is connected to

the same load, connect them in series.

2. Connect the front terminals. Orient the cup

washer so the flat surface is against the terminal.

(See Illustration 3.)

Adjustments and Calibration

The CTE-6001 is shipped with a preset “cut-out”

temperature of 135° F (57° C). The temperature

setpoint is field adjustable in a range of 100 to 250° F

(38 to 121° C).
To set “cut-out” temperature:
1. Loosen the screw in the setpoint adjustment lever.

(See Illustration 1.)

2. Slide the LEVER to the desired temperature.

NOTE: Do NOT rotate the DIAL.

3. Retighten the screw in the lever.

Maintenance

Periodically inspect the element for dirt/dust build-

up. Each component is designed for dependable,

long term reliability and performance. Careful

installation will also ensure long term reliability and

performance.

Illustration 1—Setpoint Adjustment and Dimensions

Illustration 2—Side Dimensions

Illustration 3—Terminal (Exploded View)