REE-5525 Relay Module

1

Installation Guide

Installation Guide

Proportional to Tri-State Control, Relay Module

REE-5525

Mounting 1
Sequence 1
Connections and Wiring 1
Specifications 2
Maintenance 2
Troubleshooting 2
Important Notices 2

Mounting

The module may be mounted directly to a control

box surface or in a 2 x 4" electrical handy box. Add a

blank cover to conceal the module if desired.

Connect as shown. Supply the relay with 24 VAC

(+20%/–15%, Class 2 only). (Use wire size of 14 to 22

AWG, stranded.)
NOTE: The 24 VAC sources can be the same or

separate, with no regard to phasing.

NOTE: Triac outputs are for 24 VAC loads only.

Outputs are optically isolated from the

control 24 VAC power.

Connections and Wiring

3.25

3.77

1.69

0.19

MOUNTING HOLES

0.88

1.13

FITS STANDARD 2" DEEP x 2-1/8"

UTILITY BOX & BLANK COVER PLATE

All dimensions are in inches

TYPICAL

APPLICATION

24 VAC

24 VAC

+

0–10 VDC

SIGNAL

ACTUATOR

COM CW CCW

The stage sequence operates in this manner:
• Stage 1 turns on at or below 1.5 VDC* and off at

or above 3.5 VDC. (It is on at 0 VDC.)

• Stage 2 turns on at or above 9.5 VDC* and turns

off at or below 7.5 VDC. (It is on at 10 VDC.)

Both outputs are off between 3.5 and 7.5 VDC.

Sequence

STAGE 2 ON

STAGE 1 ON

BOTH

STAGES

OFF

INPUT SIGNAL VDC

0 1.5 3.5 5 7.5 9.5 10

SEQUENCE

*NOTE: In the dark grey regions of the chart, the

stage is definitely on for the given voltage.

In the light grey regions, however, on or

off depends on the previous state. For

example, at 2 VDC, Stage 1 will be on if the

previous voltage was 0 VDC (Stage 1 on)

but off if the previous voltage was 5 VDC

(Stage 1 off).

Advertising