REE-5525 Relay Module

2

Installation Guide

Troubleshooting

• Check the wiring.
• Check the voltage from the controller, measured

from Terminal – (under 24 VAC) to Terminal

0–10 IN. (See the Sequence chart on the previous

page.)

• Check the voltage across the triac and load. (See

the chart below.)

© 2014 KMC Controls, Inc.

809-019-05A

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com

[email protected]

Important Notices

The material in this document is for information pur-

poses only. The contents and the product it describes

are subject to change without notice. KMC Controls,

Inc. makes no representations or warranties with

respect to this document. In no event shall KMC Con-

trols, Inc. be liable for any damages, direct or incidental,

arising out of or related to the use of this document.

Specifications

NOTE: Triac outputs are for 24 VAC loads only.

Maintenance

No routine maintenance is required, however protec-

tion from extremes of humidity and dirt is recom-

mended. Careful installation will also ensure long

term reliability and performance.

Supply Voltage

24 VAC (+20%/–15%) @ 1 VA

plus output loads, Class 2 only

Input Signal

0 to 10 VDC

Switching Differential 2 VDC (see Sequence chart)
Output Types

Optically isolated triacs, zero

crossing

Output Capacity

30 VAC max., 12 VA

Connections

Plated screw terminals

Wire Size

14–22 AWG, stranded

Material

Beige flame-retardant plastic

Weight

2 oz. (57 grams)

Approvals

SASO PCP Registration KSA

R-103263

Temperature Limits

Operating

32 to 120° F (0 to 49° C)

Shipping

–40 to 160° F (–40 to 71° C)

Stage Status

Normal Triac Voltage (Approximate and With Load)

Across

Load

(Actuator Common to

Terminal 1 or 2)

Across

Triac

(Terminal SC to

Terminal 1 or 2)

On

24 VAC

1 VAC

BOTH Off

0 VAC

24 VAC