1 exhaust manifold condensate drain, Benchmark 2.0ln dual-fuel low nox boiler, Gf-127 – AERCO BMK 2.0 LN Dual Fuel Serial G-11-2402 and UP User Manual

Page 15

Advertising
background image



CHAPTER 2: INSTALLATION

PR2: 04/22/13 Page 15 of 160


Benchmark 2.0LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0052_0E

GF-127

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

EXHAUST

MANIFOLD

1/2” NPT

CONDENSATE

DRAIN

CONNECTION

HOUSE-

KEEPING

PAD

BOILER

RETURN

Figure 2-4: Condensate Drain Connection Location

Exhaust Manifold Condensate Drain

2.6.1

NOTE

There are two slightly different types of condensate traps
that may be used in your configuration; an older style
without built-in adapter, and a newer style with a built-in
adapter (see Figure 2-5). Installation is the same (1/4”
threads are inside built-in adapter on newer style).

A condensate drain trap (part no. 24060) is shipped loose and must be installed at the rear of
the unit. The trap inlet and outlet contain tapped 3/4” NPT ports. The actual installation details
for the condensate trap will depend on the available clearances, housekeeping pad
height/dimensions and other prevailing conditions at the site. However, the following guidelines
must be observed to ensure proper condensate trap operation:

• The condensate trap inlet (Figure 2-5) must be level with, or lower than the exhaust manifold

drain port.

• The condensate trap must be supported to ensure that its base is level (horizontal).
• The trap must be removable for routine maintenance. AERCO recommends that a union be

utilized between the exhaust manifold condensate drain port and the trap inlet port.

1. While observing the above guidelines, connect the condensate trap inlet to the exhaust

manifold drain connection using the appropriate piping components (nipples, reducers,
elbows, etc.) for the boiler installation site.

2. At the condensate trap outlet, install a 3/4” NPT nipple.

3. Connect a length of 1” I.D polypropylene hose to the trap outlet and secure with a hose

clamp.

4. Route the hose on the trap outlet to a nearby floor drain.

If a floor drain is not available, a condensate pump can be used to remove the condensate to
drain. The maximum condensate flow rate is 20 GPH. The condensate drain trap, associated
fittings and drain line must be removable for routine maintenance.

Advertising