CHAPTER 4: INITIAL START-UP

Page 42 of 160 PR2: 04/22/13

Benchmark 2.0LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0052_0E

GF-127

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Required Tools & Instrumentation

4.2.1

The following tools and instrumentation are necessary to perform combustion calibration of the
unit:

• Digital Combustion Analyzer: Oxygen accuracy to ± 0.4%; Carbon Monoxide (CO) and

Nitrogen Oxide (NOx) resolution to 1PPM.

• 16 inch W.C. manometer or equivalent gauge and plastic tubing.
• 1/4" NPT-to-barbed fittings for use with gas supply manometer or gauge.
• Small and large flat blade screwdrivers.
• Tube of silicone adhesive

Installing Gas Supply Manometer

4.2.2

The gas supply manometer (or gauge) is used to permit the gas pressure to be monitored on
the downstream side of the SSOV during the Combustion Calibration procedures described in
paragraphs 4.5 (natural gas) or 4.6 (propane).

The gas supply manometer is installed at the upstream and/or downstream location(s) shown in
Figure 4-1.

Figure 4-1: Manometer Installation Locations

PROPANE

SSOV

NATURAL

GAS SSOV

TO AIR/FUEL

VALVE

MANUAL

SHUT-OFF

VALVE

1/4” PLUG & LEAK

DETECTION BALL VALVE

(Install manometer

here for Combustion

Calibration)