CHAPTER 3: CONTROL PANEL OPERATION

Page 40 of 160 PR2: 04/22/13

Benchmark 2.0LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0052_0E

GF-127

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Note that the energy input of the boiler is not linearly related to the Air/Fuel Valve position.
Refer to Table 3-8 for the relationship between the energy input and Air/Fuel Valve position
for a unit running on natural gas.

Table 3-8:

Relationship Between Air/Fuel Valve Position and Energy Input For Unit

Running On Natural Gas

Air/Fuel Valve Position

(% Open)

Energy Input

(BTU/Hr)

Boiler Energy Input
(% of Full Capacity)

0

0

0

10%

0

0

20%

(Stop Level)

105,000

5.0%

30%

325,000

16%

40%

590,000

30%

50%

830,000

42%

60%

1,030,000

52%

70%

1,210,000

61%

80%

1,440,000

72%

90%

1,750,000

88%

100%

2,000,000

100%

0

0

0