4 natural gas high gas pressure test, 5 propane high gas pressure test, Benchmark 2.0ln dual-fuel low nox boiler – AERCO BMK 2.0 LN Dual Fuel Serial G-11-2402 and UP User Manual

Page 65: Gf-127

Advertising
background image



CHAPTER 6: SAFETY DEVICE TESTING

PR2: 04/22/13 Page 65 of 160


Benchmark 2.0LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0052_0E

GF-127

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

6.4 NATURAL GAS HIGH GAS PRESSURE TEST

To simulate a natural gas high gas pressure fault, refer to Figure 6-1 and proceed as follows:

1. Ensure that the Fuel Selector Switch (Figure 6-2) is set to the NATURAL GAS position.

2. Remove the 1/4“ plug from the leak detection ball valve shown in Figure 6-1.

3. Install a 0 – 16” W.C. manometer (or W.C. gauge) where the 1/4” plug was removed.

4. Slowly open the leak detection ball valve

5. Start the unit in Manual mode at a valve position of 34%.

6. Slowly increase the gas pressure using the regulator adjustment screw on the natural gas

SSOV.

7. The unit should shut down and display a HIGH GAS PRESSURE fault message when the

gas pressure exceeds 10.5” W.C. The FAULT indicator should also start flashing.

8. Reduce the gas pressure back to 7.3” W.C.

9. Press the CLEAR button on the Control Box to clear the fault.

10. The fault message should clear and the FAULT indicator should go off. The unit should

restart.

11. Upon test completion, close the leak detect-ion ball valve and remove the manometer.

Replace the 1/4“ plug removed in step 2.

6.5 PROPANE HIGH GAS PRESSURE TEST

To simulate a propane high gas pressure fault, refer to Figure 6-1 and proceed as follows:

1. Ensure that the Fuel Selector Switch (Figure 6-2) is set to the PROPANE position.

2. Remove the 1/4“ plug from the leak detection ball valve shown in the upper portion of

Figure 6-1.

3. Install a 0 – 16” W.C. manometer (or W.C. gauge) where the 1/4” plug was removed.

4. Slowly open the leak detection ball valve.

5. Start the unit in Manual mode at a valve position of 34%.

6. Slowly increase the propane gas pressure using the regulator adjustment screw on the

propane SSOV.

7. The unit should shut down and display a HIGH GAS PRESSURE fault message when the

gas pressure exceeds 3.5” W.C. The FAULT indicator should also start flashing.

8. Reduce the gas pressure back to 2.8” W.C.

9. Press the CLEAR button on the Control Box to clear the fault.

10. The fault message should clear and the FAULT indicator should go off. The unit should

restart.

11. Upon test completion, close the ball valve and remove the manometer. Replace the

1/4“ plug removed in step 2.

Advertising