7 tuning menu, 8 combustion cal menu, Benchmark 2.0ln dual-fuel low nox boiler – AERCO BMK 2.0 LN Dual Fuel Serial G-11-2402 and UP User Manual

Page 35: Gf-127

Advertising
background image



CHAPTER 3: CONTROL PANEL OPERATION

PR2: 04/22/13 Page 35 of 160


Benchmark 2.0LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0052_0E

GF-127

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Table 3-4: Configuration Menu (Continued)

Aux Start On Dly

0 sec.

120 sec.

0 sec.

Failsafe Mode

Shutdown or Constant Setpt

Shutdown

*Analog Output
(See CAUTION at end of Table
3-4 )

Off, Setpoint, Outlet Temp,

Valve Position 4-20 mA,

Valve Position 0-10V

*Valve Position

0-10V

Low Fire Timer

2 sec.

600 sec.

2 sec.

Setpt Limiting

Enabled or Disabled

Disabled

Setpt Limit Band

0°F

10°F

5°F

Network Timeout

5 Sec

999 Sec

30 Sec

HI DB Setpt EN

0%

100%

30%

Demand Offsert

0

25

10

Deadband High

0

25

2

Deadband Low

0

25

2

*CAUTION!

DO NOT CHANGE the Analog Output Menu Item from its
Default setting (Valve Position 0-10V).

3.7 TUNING MENU

The Tuning Menu items in Table 3-5 are Factory set for each individual unit. Do not change
these menu entries unless specifically requested to do so by Factory-Trained personnel.

3.8 COMBUSTION CAL MENU

The Combustion Cal (Calibration) Menu items in Table 3-6 are used to vary the speed of
the unit’s blower motor based on air temperature and air density at prescribed Air/Fuel
Valve positions (% open). This is accomplished by providing a DC drive voltage to the
motor which adjusts the rotational speed of the blower to maximize combustion efficiency
and ensure the unit conforms to the Nitrogen Oxide (NOx) and Carbon Monoxide (CO)
emissions specified in Chapter 4. The valve positions (%) and default drive voltages are
listed in Table 3-6.

Table 3-5: Tuning Menu

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

Prop Band

1°F

120°F

70°F

Integral Gain

0.00

2.00

1.00

Derivative Time

0.0 min

2.00 min

0.00 min

Reset Defaults?

Yes, No, Are You Sure?

No

Advertising