CHAPTER 6: SAFETY DEVICE TESTING

Page 64 of 160 PR2: 04/22/13

Benchmark 2.0LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0052_0E

GF-127

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288



Figure 6-1: Low & High Gas Pressure Testing

6.3 PROPANE LOW GAS PRESSURE FAULT TEST

Refer to Figure 6-1 and ensure that the leak detection ball valve located at the high gas
pressure switch is closed.

1. Ensure that the Fuel Selector Switch (Figure 6-2) is set to the PROPANE position.

2. Remove the 1/4“ plug from the ball valve at the propane low gas pressure switch shown in

the upper-left portion of Figure 6-1.

3. Install a 0 – 16 “ W.C. manometer or a W.C. gauge where the 1/4" plug was removed.

4. Slowly open the ball valve near the propane low gas pressure switch.

5. Place the unit in Manual Mode and adjust the valve position to 34%.

6. While the unit is firing, slowly close the external manual gas shut-off valve.

7. The unit should shut down and display a LOW GAS PRESSURE fault message at

approximately 8.5” W.C. The FAULT indicator should also start flashing.

8. Fully open the external manual gas shut-off valve and press the CLEAR button on the

Control Box.

9. The fault message should clear and the FAULT indicator should go off. The unit should

restart.

10. Upon test completion, close the ball valve and remove the manometer. Replace the 1/4“

plug removed in step 2.

NATURAL
GAS
SSOV

1/4” PLUG & LEAK
DETECTION BALL VALVE
(Install manometer
here for High Gas Pressure
Tests)

PROPANE SSOV

PROPANE LOW

GAS PRESSURE

SWITCH

NATURAL GAS HIGH
GAS PRESSURE SWITCH

PROPANE GAS HIGH
GAS PRESSURE SWITCH

NATURAL
GAS LOW

GAS PRESSURE
SWITCH

1/4” PLUG

(Install manometer

here for Propane Low

Gas Pressure Test)

1/4” PLUG
(Install manometer
here for Natural
Gas Low Gas
Pressure Test)

PROPANE

INLET

NATURAL
GAS INLET

MANUAL GAS
SHUT-OFF VALVE