CHAPTER 5: MODE OF OPERATION

Page 62 of 160 PR2: 04/22/13

Benchmark 2.0LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0052_0E

GF-127

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Replay Panel (optional, depending on application), and the RS485 Comm terminals in the I/O
box. Wire the units using a shielded twisted pair of 18 to 22 AWG wire. When wiring multiple
units, each unit’s wiring must conform to the above. For a complete CCP system-wiring diagram
see the AERCO CCP-1 literature (BMS 168 applications) and TAG-0050 (ACS).

Combination Control System Setup and Startup

5.7.2

Setup for the Combination Mode requires entries to be made in the Configuration Menu for
boiler mode, remote signal type and setpoint. The setpoint is adjustable from 40°F to 240°F.

Enter the following settings in the Configuration Menu:

MENU OPTION

SETTINGS

BMS 168 Applications

ACS Applications

Boiler Mode

Combination

Combination

Remote Signal

BMS (PWM Input)

Network (RS485)

Internal Setpt

40°F to 240°F

40°F to 240°F

Refer to paragraph 3.3 for instructions on changing menu options.

While it is possible to change other temperature-related functions for combination mode, thes
functions are preset to their factory default values. These default settings work well in most
applications. It is suggested that AERCO be contacted prior to changing settings other than the
unit’s setpoint. For a complete listing of temperature related function defaults, see Appendix E.

To set the unit to the manual mode, press the AUTO/MAN switch. The MANUAL LED will light.

To set the unit back to the auto mode, press the AUTO/MAN switch. The MANUAL LED will go
off and the REMOTE LED will light.

When the boiler is switched to BMS mode, the AERCO BMS/ACS controls the valve position.
There are no setup requirements to the boiler(s) in this mode.