CONTROL PANEL OPERATING PROCEDURES

3-8

3.7 TUNING MENU

The Tuning Menu items in Table 3-5 are Factory

set for each individual unit. Do not change

these menu entries unless specifically requested

to do so by Factory-Trained personnel.

3.8 COMBUSTION CAL MENU

The Combustion Cal (Calibration) Menu items in

Table 3-6 are used to vary the speed of the

unit’s blower motor based on air temperature

and air density at prescribed firing rates. This is

accomplished by providing a DC drive voltage to

the motor which adjusts the rotational speed of

the blower to maximize combustion efficiency

and ensure the unit conforms to the Nitrogen

Oxide (NOx) and Carbon Monoxide (CO)

emissions specified in Chapter 4. The firing

rates (%) and default drive voltages are listed in

Table 3-6.

Table 3-5. Tuning Menu

Available Choices or Limits

Menu Item Display

Minimum

Maximum

Default

Prop Band

1°F

120°F

70°F

Integral Gain

0.00

2.00

1.00

Derivative Time

0.0 min

2.00 min

0.00 min

Reset Defaults?

Yes, No, Are You Sure?

No

Table 3-6. Combustion Cal Menu

Available Choices or Limits

Menu Item Display

Minimum

Maximum

Default

CAL Voltage 16%

.25

8.20

1.80v

CAL Voltage 30%

.25

8.20

3.20v

CAL Voltage 45%

.25

8.20

3.70v

CAL Voltage 60%

.25

8.20

3.80

CAL Voltage 80%

.25

8.20

4.60

CAL Voltage 100%

.25

8.20

6.00

SET Valve Position

0%

100%

0%

Blower Output

Monitor Blower Output Voltage

.00

3.9 START SEQUENCE

When the Control Box

ON/OFF switch is set to

the ON position, it checks all pre-purge safety

switches to ensure they are closed. These

switches include:

Safety Shut-Off Valve Proof of Closure

(POC) switch

Low Water Level switch

High Water Temperature switch

High Gas Pressure switch

Low Gas Pressure switch

Blower Proof switch

Blocked Inlet switch

If all of the above switches are closed, the

READY light above the ON/OFF switch will light

and the unit will be in the Standby mode.
When there is a demand for heat, the following

events will occur:

NOTE

If any of the Pre-Purge safety device

switches are open, the appropriate fault

message will be displayed. Also, the

appropriate fault messages will be displayed

throughout the start sequence, if the

required conditions are not observed.
1. The

DEMAND LED status indicator will light.