RS232 COMMUNICATION

9-2

10. To display the Fault (F) Log, Sensor (S) Log

or Time (T) Line Log, press F, S or T

followed by <Rtn>. Refer to paragraph 9.4 for

descriptions and samples of these data logs.

11. To log off and terminate the RS232 com-

munication link, press L followed by <Rtn>.

9.4 DATA LOGGING

During operation, the C-More Control Panel

continuously monitors and logs data associated

with operational events, faults and sensor

readings associated with the boiler or water

heater system. Descriptions of these data logs

are provided in the following paragraphs. The

basic procedure for accessing each data log is

described in paragraph 9.3, step 7.

9.4.1 Fault Log

The C-More Control Panel logs the last 20 faults

(0 – 19) starting with the most recent (#0). They

can be viewed in the front panel display or via

the RS232 port. The Fault Log cannot be

cleared. If the Fault Log already contains 10

faults, the earliest fault is overwritten when a

new fault occurs. A sample Fault Log display is

shown in Table 9-1.

NOTE:

The Operation Time (T) Log can store

thousands of records. Therefore, to view

the most recently logged record, enter “T”

followed by 0 (zero) and press Enter

(i.e. T0 <Enter>). To view earlier records

in reverse chronological order, enter T

and press Enter. To go back 200 or 1000

records, enter T200 or T1000, etc. and

press Enter.


9.4.2 Operation Time Log

The Operation Time Log consists of a string of

ASCII records stored in non-volatile memory

within the C-More Control Panel. Events such

as power-up, ignition and turn-off are time

stamped. Data logged while the unit is running

are run-length encoded. Data is logged or the

run-length incremented every 30 seconds. For a

new run record to be logged, the fire rate or

flame strength must change by more than 5%,

or the run mode must change. At steady-state,

the run-length is allowed to reach a maximum of

30 minutes before the record is logged. This

means that no more than 30 minutes of data can

be lost if the unit loses power. Table 9-2 shows

a sample Operation Time Log for a boiler:
The Operation Time Log can only be accessed

through the RS232 interface using a laptop or

other terminal device. Ten operation time

records are displayed for each T command

entry. The operation time log can be cleared

ONLY by factory authorized personnel using the

Clear Log option in the Factory menu.

NOTE:

The Sensor (S) Log can store up to 1200

records. Therefore, to view the most

recently logged record, enter “S” followed

by 0 (zero) and then press Enter (i.e. S0

<Enter>). To view earlier records in

reverse chronological order, enter S and

press Enter. To go back 200 or 700

records, enter S200 or S700, etc. and

press Enter.

9.4.3 Sensor Log

The sensor values can be logged at a different

rate if needed by setting the Sensor Log Interval

in the Diagnostics Menu. The log interval can

vary from once every minute to once every day.

Table 9-3 shows a sample Sensor Log every 5

minutes for a boiler running in Constant Setpoint

mode.