SAFETY DEVICE TESTING

6-1

CHAPTER 6 SAFETY DEVICE TESTING

6.1 TESTING OF SAFETY DEVICES

Periodic safety device testing is required to

ensure that the control system and safety

devices are operating properly. The Benchmark

3.0 Dual-Fuel control system comprehensively

monitors all combustion-related safety devices

before, during and after the start sequence. The

following tests check to ensure that the system

is operating as designed.
Operating controls and safety devices should be

tested on a regular basis or following service or

replacement. All testing must conform to local

codes such as ASME CSD-1.

NOTE

MANUAL and AUTO modes of operation

are required to perform the following

tests. For a complete explanation of these

modes, see Chapter 3.

NOTE

It will be necessary to remove the front

door and side panels from the unit to

perform the following tests.

WARNING

ELECTRICAL VOLTAGES IN THIS

SYSTEM MAY INCLUDE 460, 220,

120 AND 24 VOLTS AC. POWER

MUST BE REMOVED PRIOR TO

PERFORMING WIRE REMOVAL OR

OTHER TEST PROCEDURES THAT

CAN RESULT IN ELECTRICAL

SHOCK.

6.2 NATURAL GAS LOW GAS

PRESSURE SWITCH TEST

Refer to Figure 6-1 and ensure that the leak

detection ball valve located at the top of the gas

train by the high gas pressure switches is

closed.
1. Ensure that the Fuel Selector Switch (Figure

4-3) is set to the NATURAL GAS position.

2. Remove the 1/8 “ plug from the ball valve at

the natural gas low gas pressure switch

shown in the lower-left portion of Figure 6-1.

3. Install a 0 – 16 “ W.C. manometer or a W.C.

gauge where the 1/8" plug was removed.

4. Slowly open the ball valve near the low gas

pressure switch.

5. Place the unit in Manual Mode and adjust

the valve position between 25 and 30%.

6. While the unit is firing, slowly close the

external manual gas shut-off valve.

7. The unit should shut down and display a

LOW GAS PRESSURE fault message at

approximately 2.6” W.C. The

FAULT indi-

cator should also start flashing.

1/8" NPT PLUG

(INSTALL MANOMETER HERE FOR

HIGH GAS PRESSURE TEST)

LEAK DETECTION

BALL VALVE

PROPANE HIGH

GAS PRESSURE

SWITCH

NATURAL

GAS SSOV

PROPANE

SSOV

NATURAL GAS

LOW GAS

PRESSURE

SWITCH

BALL

VALVE

STAGED IGNITION

1/4" BALL VALVE

NAT. GAS &

PROPANE

PRESSURE

REGULATOR

FEEDBACK

LINES

NATURAL GAS

HIGH GAS

PRESSURE

SWITCH

PROPANE

INLET

NAT. GAS

INLET

PROPANE

LOW GAS

PRESSURE

SWITCH

1/8" NPT PLUG

(INSTALL MANOMETER

HERE FOR GAS

PRESSURE TEST)

Figure 6-1

Low & High Gas Pressure Testing

8. Fully open the external manual gas shut-off

valve and press the

CLEAR button on the

Control Box.

9. The fault message should clear and the

FAULT indicator should go off. The unit

should restart.

10. Upon test completion, close the ball valve

and remove the manometer. Replace the

1/8 “ plug removed in step 2.