Chapter 9 rs232 communication, 1 introduction, 2 rs232 communication setup – AERCO BMK 3.0 LN Dual-Fuel Series Gas Fired Low NOx Boiler System User Manual

Page 77: 3 menu processing utilizing rs232 communication, Rs232 communication

Advertising
background image

RS232 COMMUNICATION

9-1

CHAPTER 9 RS232 COMMUNICATION

9.1 INTRODUCTION

The RS232 port on the front panel of the C-More

Control Box (Figure 3-1) can be interfaced to a

laptop computer or other suitable terminal using

a RS232 adapter cable. RS232 communication

can be accomplished using any “Dumb

Terminal” emulation, such as “Hyper Terminal”

which is included with Microsoft Windows. The

RS232 communication feature permits viewing

or changing of Control Panel menu options and

also provides access to data logs showing Event

Time Line, Fault and Sensor log displays.

9.2 RS232 COMMUNICATION SETUP

Regardless of the terminal emulation utilized,

the following guidelines must be adhered to

when setting up the RS232 communication link:
1. Baud Rate – The baud rates which can be

used with the C-More Control Panel are:

2400
4800
9600 (Default)
19.2K
2. Data Format – The program must be set for:

8 data bits, 1 stop bit, no parity and either

Xon/Xoff or No flow control.

9.3 MENU PROCESSING UTILIZING

RS232 COMMUNICATION

Viewing data logs and viewing or changing

Control Panel menu options using RS232

communication is accomplished as follows:
1. Start the emulator software program and

ensure that the specified baud rate and data

formats have been entered.

2. Press the Enter key on the laptop. An

asterisk (*) prompt should appear.

3. At the prompt, enter the valid RS232

password (jaguar) in lower case letters and

press Enter.

4. “Welcome to Aerco” will appear in the laptop

or “dumb terminal” display with a listing of

the following available entry choices:

M = Display next Menu

D = Display menu items

N = Display next menu items

Cxx = Change item xx

F = Fault log display

S = Sensor log display

T = Time line display

L = Log off

NOTE:

The Level 1 password (159) must be

entered to change options in the Setup,

Configuration and Tuning Menus. The

Level 2 password (6817) must be entered

to view or change options in the

Calibration and Diagnostics Menus.
With the exception of the password entry,

all other keyboard entries can be made

using either upper or lower case.

5. To view the available menus in the top-down

sequence shown in Figure 3-2, enter M

<Rtn>. The Menu title and first 10 options

will be displayed.

6. When viewing menus containing more than

10 options, enter N <Rtn> to display the

remaining options.

7. Shortcut keys are also available to go directly

to a specific menu. These shortcut keys are:
m0

Default (Operating) Menu

m1

Setup Menu

m2

Configuration Menu

m3

Tuning Menu

m4

Calibration Menu

m5

Diagnostic Menu

8. To change a value or setting for a displayed

menu option, proceed as follows:

(a) Enter C, followed by the number to the

right of the displayed option to be

changed, and then press <Rtn>.

(b) Enter the desired value or setting for the

option and press <Rtn>. Refer to

Chapter 3, Tables 3-2 through 3-5 for

allowable entry ranges and settings for

the Operating, Setup, Configuration and

Tuning Menus. (The Calibration and

Diagnostic Menus should only be used

by Factory-Trained service personnel).

(c) Menu changes will be stored in non-

volatile memory.

9. To redisplay the menu and view the option

which was just changed in step 5, enter D

and press <Rtn>.

Advertising