Chapter 7 maintenance, 1 maintenance schedule, 2 ignitor-injector – AERCO BMK 3.0 LN Dual-Fuel Series Gas Fired Low NOx Boiler System User Manual

Page 57: Maintenance

Advertising
background image

MAINTENANCE

7-1

CHAPTER 7 MAINTENANCE

7.1 MAINTENANCE SCHEDULE

The unit requires regular routine maintenance to

keep up efficiency and reliability. For best

operation and life of the unit, the following

routine maintenance procedures should be

carried out in the time periods specified in Table

7-1. See Appendix I for a complete CSD-1

inspection check list.
In order to perform the maintenance tasks

specified in Table 7-1, the following

maintenance kits are available through your

local AERCO Sales Representative:

Annual Maintenance Kit, Part No. 58025-01

24-Month Waterside/Fireside Inspection Kit,

Part No. 58025-04 (See NOTE below)

NOTE

The 24-Month Waterside/Fireside Inspec-

tion Kit also includes the items contained

in the Annual Maintenance Kit. Therefore,

only Kit Part No. 58025-04 is required

when performing the waterside/fireside

inspections.


Appendix K contains recommended spare parts

lists for maintenance of the boiler.

WARNING

TO AVOID PERSONAL INJURY,

PRIOR TO SERVICING:

DISCONNECT THE AC SUPPLY BY

TURNING OFF THE SERVICE

SWITCH AND AC SUPPLY CIRCUIT

BREAKER.

SHUT OFF THE GAS SUPPLY AT

THE MANUAL SHUT-OFF VALVE

PROVIDED WITH THE UNIT

ALLOW THE UNIT TO COOL TO A

SAFE WATER TEMPERATURE TO

PREVENT BURNING OR SCALDING

7.2 IGNITOR-INJECTOR

The ignitor-injector (part no. 58023) is located in

the body of the burner (see Figure 7-1). In

addition to providing the ignition spark required

to light the burner, this component also contains

a gas injector tube which connects to the staged

ignition assembly. The ignitor-injector may be

hot, therefore, care should be exercised to avoid

burns. It is easier to remove the ignitor-injector

from the unit after the unit has cooled to room

temperature.

BURNER

HOUSING

FLAME DETECTOR

& GASKET (SECURED

WITH 2 SCREWS)

IGNITOR-

INJECTOR

STAGED

IGNITION

ASSY

Figure 7-1.

Burner Assembly – Top View

To inspect/replace the Ignitor-injector, proceed

as follows:
1. Set the

ON/OFF switch on the control panel,

to the

OFF position. Disconnect AC power

from the unit

2. Remove the top and side panels from the

unit.

3. Disconnect the cable from the ignitor-injector.

4. Using a 7/16” open-end wrench, disconnect

the compression nut securing the gas injector

tube of the ignitor-injector to the elbow of the

staged ignition assembly. Disconnect the

staged ignition assembly from the ignitor-

injector.

Advertising