Table 8-1. boiler troubleshooting – continued, Troubleshooting – AERCO BMK 3.0 LN Dual-Fuel Series Gas Fired Low NOx Boiler System User Manual

Page 71

Advertising
background image

TROUBLESHOOTING

8-9

TABLE 8-1. BOILER TROUBLESHOOTING – Continued

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

PRG SWTCH CLOSED

DURING IGNITION

1. A/F Valve rotated open to purge and did

not rotate to ignition position

2. Defective or shorted switch.

3. Switch wired incorrectly.
4. Defective Power Supply Board or fuse

5. Defective IGST Board

1. Start the unit. The Air/Fuel Valve should rotate to the purge

(open) position, then back to ignition position (towards closed)

during the ignition cycle. If the valve does not rotate back to the

ignition position, check the Air/Fuel Valve calibration. If

calibration is okay, the problem may be in the Air/Fuel Valve or

the Control Box. Refer fault to qualified service personnel.

2. If the Air/Fuel Valve does rotate to the ignition position, check the

purge switch for continuity between the N.O. and COM terminals.

If the switch shows continuity when not in contact with the cam,

check to ensure that the switch is wired correctly (correct wire

numbers on the normally open terminals).

3. If the switch is wired correctly, replace the switch.
4. Check DS1 & DS2 LEDs on Power Supply Board. If they are not

steady ON, replace Power Supply Board.

5. Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF

every second. If not, replace IGST Board.

PRG SWTCH OPEN

DURING PURGE

1. Defective purge switch.

2. No voltage present at switch.

3. Switch wired incorrectly.

4. Defective Power Supply Board or fuse

5. Defective IGST Board

1. If the air-fuel valve does rotate, check the purge switch for

continuity when closing. Replace switch if continuity does not exist.

2. Measure for 24 VAC from each side of the switch to ground. If

24VAC is not present, refer fault to qualified service personnel.

3. Check to ensure that the switch is wired correctly (correct wire

numbers on the normally open terminals).

4. Check DS1 & DS2 LEDs on Power Supply Board. If they are not

steady ON, replace Power Supply Board.

5. Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF

every second. If not, replace IGST Board.

OUTDOOR TEMP

SENSOR FAULT

1. Loose or broken wiring.
2. Defective Sensor.

3. Incorrect Sensor.

1. Inspect Outdoor Temperature sensor for loose or broken wiring.
2. Check resistance of sensor to determine if it is within specification.

3. Ensure that the correct sensor is installed.

REMOTE SETPT

SIGNAL FAULT

1. Remote setpoint signal not present:

Not yet installed.

Wrong polarity.

Signal defective at source.

Broken or loose wiring.

1. Check I/O Box to ensure signal is hooked up.

Hook up if not installed.

If installed, check polarity.

Measure signal level.

Check continuity of wiring between source and boiler.

Advertising