AERCO Innovation (G-13-1854 and above) User Manual
Page 119

Innovation Water Heaters Installation, Operation & Maintenance Manual
CHAPTER 9 – WATER HEATER MANAGEMENT
OMM-0078_0J
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Page 119 of
196
GF-128
Phone: 800-526-0288
PRI: 11/22/2013
Figure 9-6. Actuator PC Board Components
Power must be removed from the Actuator prior to attempting to disengage
the clutch. Failure to observe this precaution may damage the Actuator.
The PC board also contains a brass button which is used to disengage the clutch and permit the
ball valve to be manually rotated. To disengage the clutch, proceed as follows:
Actuator Clutch Disengagement
1. Disconnect the 3-pin connector on the Actuator to ensure that 24 VAC power is not being
supplied
2. Press and hold the brass CLUTCH button shown in Figure 9-6.
3. With the CLUTCH button depressed, the ball valve can be manually rotated from the fully
open (90°) to the fully closed (0°) position.