AERCO Innovation (G-13-1854 and above) User Manual

Page 97

Advertising
background image

Innovation Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 7 – TROUBLESHOOTING GUIDE

OMM-0078_0J

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 97 of

196

GF-128

Phone: 800-526-0288

PRI: 11/22/2013

TABLE 7-1. WATER HEATER TROUBLESHOOTING – Continued

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

RESIDUAL

FLAME

1.

SSOV not fully closed.

2.

Defective Flame Detector

1.

Check open/close indicator window of Safety Shut-Off Valve
(SSOV) and ensure that the SSOV is fully closed. If not fully
closed, replace the valve and or actuator.

Close the 1” Gas Shut-Off Valve downstream of SSOV (Figure 7-
1). Install a manometer or gauge at the leak detection port
between the SSOV and Gas Shut Off Valve. If a gas pressure
reading is observed replace the SSOV Valve and/or Actuator.

2.

Replace Flame Detector.

SSOV FAULT DURING

PURGE

See SSOV SWITCH OPEN

SSOV FAULT

DURING RUN

SSOV switch closed for 15 seconds
during run.

Replace or adjust microswitch in SSOV actuator. If fault persists,
replace actuator.

SSOV RELAY

FAILURE

1.

SSOV relay failed on IGST board.

2.

Floating Neutral.


3.

Hot and Neutral reversed at SSOV.

1.

Press CLEAR button and restart unit. If fault persists, replace
Ignition/Stepper (IGST) Board.

2.

The Neutral and Earth Ground are not connected at the source
and therefore there is a voltage measured between the two. This
measurement should be near zero or no more than a few
millivolts.

3.

Check SSOV power wiring.

SSOV

SWITCH OPEN

1.

Actuator not allowing for full
closure of gas valve

2.

SSOV powered when it should not
be

3.

Defective Switch or Actuator

4.

Incorrectly wired switch.

1.

Observe operation of the Safety Shut-Off Valve (SSOV) through
indicator on the Valve actuator and ensure that the valve is fully
and not partially closing.

2.

If the SSOV never closes, it may be powered continuously. Close
the gas supply and remove power from the unit. Refer fault to
qualified service personnel.

3.

Remove the electrical cover from the SSOV and check switch
continuity. If the switch does not show continuity with the gas
valve closed, either adjust or replace the switch or actuator.

4.

Ensure that the SSOV Proof of Closure switch is correctly wired.

Advertising