8 pressure & temperature relief valve installation, 9 condensate drain & piping – AERCO Innovation (G-13-1854 and above) User Manual

Page 24

Advertising
background image

Innovation Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 2 – INSTALLATION

Page 24 of

196

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0078_0J

PRI: 11/22/2013

Phone: 800-526-0288

GF-128

2.8 PRESSURE & TEMPERATURE RELIEF VALVE INSTALLATION

An ASME rated Pressure & Temperature (P&T) Relief Valve is supplied with each Innovation
Water Heater. With the exception of Alberta installations (see above Note), the valve setpoint is
150 psig/210°F. The P&T Relief Valve is installed on the hot water outlet at the top of the
Recirculation Loop Assembly as shown in Figure 2-5. A suitable pipe joint compound should be
used on the threaded connections. Any excess should be wiped off to avoid getting any into the
valve body. The relief valve should be piped to within 12 inches of the floor to prevent injury in
the event of a discharge. The relief outlet piping must be equal to the outlet size of the relief
valve without reduction. No valves, restrictions, or other blockages are allowed in the discharge
line. In multiple unit installations the discharge lines must not be manifolded together. Each
must be individually run to a suitable discharge location.

2.9 CONDENSATE DRAIN & PIPING

The Innovation Water Heater is designed to condense water vapor from the flue products.
Therefore, the installation must have provisions for suitable condensate drainage or collection.

The condensate drain port is located on the exhaust manifold at the rear of the unit (Figure 2-6).
This drain port must be connected to the Condensate Trap (part no. 24060) which is packed
separately within the unit’s shipping container. The Condensate Trap inlet and outlet
connections contain tapped 3/4” NPT ports.

PARTIAL REAR VIEW

Figure 2-6. Condensate Drain Connection Location

A sample Condensate Trap installation is shown in Figure 2-7. However, the actual installation
details for the trap will vary depending on the available clearances, housekeeping pad height/
dimensions and other prevailing conditions at the site. The following general guidelines must be
observed to ensure proper condensate drainage:

• The condensate trap inlet (Figure 2-7) must be level with, or lower than the exhaust

manifold drain port.

• The base of the condensate trap must be supported to ensure that it is level (horizontal).

COLD WATER

INLET 2” NPT

DRAIN VALVE

AIR INLET

EXHAUST MANIFOLD

CONDENSATE DRAIN

CONNECTION (3/4” NPT)

Advertising