AERCO Innovation (G-13-1854 and above) User Manual
Page 134

Innovation Water Heaters Installation, Operation & Maintenance Manual
APPENDIX D – INNOVATION DEFAULT SETTINGS
Page 134 of
196
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
OMM-0078_0J
PRI: 11/22/2013
Phone: 800-526-0288
GF-128
INNOVATION DEFAULT SETTINGS - Continued
MENU & OPTION
FACTORY DEFAULT
Tuning Menu
Prop Band
8°F
Integral Gain
1.60
Derivative Time
0.10 min
Min Load Adj
0°F
Max Load Adj
0°F
FFWD Temp
N/A
Outlet Feedback
On
Feedback Gain
0.05
Breakpoint At 100%
85°F
Breakpoint At 90%
86°F
Breakpoint At 80%
87°F
Breakpoint At 70%
88°F
Breakpoint At 60%
89°F
Breakpoint At 50%
90°F
Breakpoint At 40%
94°F
Breakpoint At 30%
103°F
Breakpoint At 20%
118°F
Breakpoint At 10%
134°F
Breakpoint At 0%
136°F
Reset Defaults?
No