Innovation Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 6 – MAINTENANCE

OMM-0078_0J

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 85 of

196

GF-128

Phone: 800-526-0288

PRI: 11/22/2013


Figure 6-10. Air Filter Mounting Location

6.11 SHUTTING THE WATER HEATER DOWN FOR AN EXTENDED PERIOD OF
TIME

If the heater is to be taken out of service for an extended period of time (one year or more),
complete the following instructions.

Extended Period Shut-Down

1. Set ON/OFF switch on the front panel to the OFF position to shut down the heater’s

operating controls.

2. Disconnect AC power from the unit.

3. Close the water inlet and outlet valves to isolate unit.

4. Close external gas supply valve.

5. Open relief valve to vent water pressure.







BARE HEATER – PARTIAL FRONT VIEW

AIR FILTER

FILTER CLAMP

AIR/FUEL

VALVE

BLOWER
MOTOR