9.9.2 Sequencing Valve Operating Characteristics

The Sequencing Valve is powered by 24 VAC which is supplied from a step-down transformer
located in the Power Box of the Innovation Water Heater. The 24 VAC power output and a 0 to
20 mA control signal from the I/O Box of the Water Heater are routed to the Sequencing Valve
via a 3-pin Molex connector.

During normal Water Heater Management (WHM), a control signal of less than (<) 4 mA will
rotate the valve to the fully open (0°) position. Conversely, a control signal above 14 mA will
rotate the valve to the fully closed (90°) position. The valve position can be observed on the
scale provided on the Actuator Linkage.