9 ssov proof of closure switch – AERCO Innovation (G-13-1854 and above) User Manual

Page 68

Advertising
background image

Innovation Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 5 – MODE OF OPERATION

Page 68 of

196

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0078_0J

PRI: 11/22/2013

Phone: 800-526-0288

GF-128

PARTIAL REAR VIEW

Figure 5-5. Water Heater Rear View Showing Air Inlet Location

5.9 SSOV PROOF OF CLOSURE SWITCH

The SSOV shown in Figure 5-1 contains the proof of closure switch. The proof of closure switch
circuit is checked as follows:

SSOV Proof of Closure Switch

1. Set the unit’s ON/OFF switch to the OFF position.

2. Place the unit in Manual Mode and set the valve position between 25% and 30%

3. Refer to Figure 5-1 and locate the SSOV.

4. Remove the cover from the SSOV by loosening the screw shown in Figure 5-6. Lift off the

cover to access the terminal wiring connections.

5. Disconnect wire #148 from the SSOV to “open” the proof of closure switch circuit.

6. The unit should fault and display SSOV SWITCH OPEN.

7. Replace wire #148 and press the CLEAR button.

8. Set the ON/OFF switch to ON to start the unit.

9. Remove the wire again when the unit reaches the purge cycle and PURGING is

displayed.

10. The unit should shut down and display SSOV FAULT DURING PURGE.

11. Replace the wire on the SSOV and press the CLEAR button. The unit should restart.

AIR INLET

EXHAUST

MANIFOLD

COLD WATER
INLET

DRAIN VALVE

Advertising