BASO BGH2UNCNTRLHT-01 User Manual

Page 14

Advertising
background image

14

BGH2UNCTRLHT-01 Universal Hot Surface Ignition Control Installation Instructions

Yes

No

No

Yes

Turn on power

and gas.

Close thermostat

contacts.

Module LED

did not light?

Module LED

blinks green?

24V between

24V and 24V(GND)

terminals?

Yes

No

Yes

No

Check transformer,

thermostat and wiring.

Repair or replace as needed.

Replace

module.

Yes

No

No

Yes

Replace

module.

Yes

Yes

No

No

Yes

No

Replace

module.

LED blinks

1, 3, or 5 quick red

flashes, then

pause?

Replace
module.

LED blinks

2 quick red

flashes, then

pause?

LED blinks

4 quick red

flashes, then

pause?

No

Check wiring to igniter.

Check igniter for short

or malfunction and

replace if necessary.

Check line

voltage.

Yes

Igniter didn’t turn

on during igniter

warmup mode?

120 VAC

between HSI (HOT)

and L2 (NEUT)

during igniter

warmup?

Check wiring to igniter.

Check igniter and replace

if necessary.

Main burner

failed to light

during trial for

ignition?

LED blinks

3 quick red

flashes, then

pause?

Replace

module.

No

Replace

module.

24 VAC

between VALVE

and VALVE (GND)

terminals during trial

for ignition?

Yes

Gas at

main burner?

Adjust burner flame

size or position, adjust

igniter position, or

replace main burner.

Yes

Check shutoff valves are on.

Check wiring to main valve.

Check tubing is clear.

If all OK, replace main valve.

No

After burner

is lit, does valve

turn off and start

new cycle?

Main flame

in contact with

igniter?

Yes

No

Main burner

grounded to GND

(BURNER)?

Adjust main flame size

or igniter position.

No

No

Yes

Assure main burner

is properly grounded.

Remote

flame sense?

Check wiring to

REMOTE (SENSE) terminal.

If OK, replace module.

Replace

module.

Yes

No

Yes

Control is
operating

normally.

Figure 5

: BGH Universal Series HSI (Hot Surface Ignition) Control Troubleshooting Flowchart