BASO BGH2UNCNTRLHT-01 User Manual
Page 16
Advertising
16
BGH2UNCTRLHT-01 Universal Hot Surface Ignition Control Installation Instructions
Cut out and leave near control.
Green LED Indications During Normal Operation
Steady On
Flame detected, Good flame, Main burner on
0.5 Second On, 0.5 Second Off
Pre-purge, Between trial purge, Igniter warmup
2 Continuous Quick Flashes
Flame detected, Weak flame, Main burner on
Red LED Indications During Error Operation
1 Flash, then pause
Flame Error
Lockout
3 Flashes, then pause
Gas Valve Error
Lockout
4 Flashes, then pause
Line Voltage/Frequency Error
Standby
5 Flashes, then pause
Internal Control Error
Lockout
Advertising