BGH2UNCTRLHT-01 Universal Hot Surface Ignition Control Installation Instructions 3

Table 1: BGH2UNCNTRLHT-01 Universal Cross Reference

Switch

Positions

ON

Switch

Positions

OFF

White-Rodgers Robershaw Honeywell Fenwal

2 1,3,4,5

50E47-130 to 139

50E47-330 t 339

2,5 1,3,4

50E47-120 to 129
50E47-320 to 329

2,4 1,3,5

50F47-130 to 139
50F47-330 to 339

2,4,5 1,3

50F47-120 to 129
50F47-320 to 329

05-356225-153(d,g)
05-356225-154(d,g)
05-356225-155(d,g)

2,3 1,4,5

50E47-110 to 119
50E47-310 to 319

50F47-110 to 119
50F47-310 to 319

2,3,5 1,4

50E47-101 to 109
50E47-301 to 309

50F47-101 to 109
50F47-301 to 309

HS780-17NL-108A(a)

05-356225-053(c,d)
05-356225-054(c,d)
05-356225-055(c,d)

2,3,4 1,5

8910U

S890D1006(a,e)
S890C1007(a,e)

2,3,4,5 1

― HS780-34NL-108A(a)

S89D1002(a)
S89C1004(a)

S89J1008(a)

S89C1012(a)

1 2,3,4,5

50E47-50 to 59

50E47-250 to 259

Note: For timing parameters see Table 2.
(a)

The BGH2UNCNTRLHT-01 Universal and the referenced control ignition trial times are different; however, the
ignition trial time is within the design tolerance of the referenced control.

(b)

The BGH2UNCNTRLHT-01 Universal between trial purge time is longer than that of the referenced control.

(c)

The BGH2UNCNTRLHT-01 Universal between trial purge and igniter warmup times is longer than those of the
referenced control.

(d)

The BGH2UNCNTRLHT-01 Universal ignition trial time is shorter than that of the referenced control. Be sure
to observe appliance operation to assure reliable performance.

(e)

The BGH2UNCNTRLHT-01 Universal pre-purge time is longer than that of the referenced control

(f)

The BGH2UNCNTRLHT-01 Universal pre-purge and between trial purge times are longer than those of the
referenced control.

(g)

The BGH2UNCNTRLHT-01 Universal pre-purge, between trial purge, and igniter warmup times are longer
than those of the referenced control.