Chapter 3 Installing the Cisco AS5400XM Universal Gateway

Supplying Power

Warning

A readily accessible two-poled disconnect device must be incorporated in the fixed wiring.
Statement 1022

Warning

Before performing any of the following procedures, ensure that power is removed from the DC circuit.
Statement 1003

Warning

Before connecting or disconnecting ground or power wires to the chassis, ensure that power is
removed from the DC circuit. To ensure that all power is OFF, locate the circuit breaker on the panel
board that services the DC circuit, switch the circuit breaker to the OFF position, and tape the switch
handle of the circuit breaker in the OFF position.
Statement 140

Note

This product is intended for installation in restricted access areas and is approved for connection using
12 or 14 AWG copper conductors only. The installation must comply with all applicable codes.

See

Figure 3-15

and follow these steps to wire the terminal blocks:

Step 1

Note the orientation of the DC power supply. The power supply cord should have three wires: 48 VDC
Return, –48 VDC, and a safety ground (green wire).

Warning

The illustration shows the DC power supply terminal block. Wire the DC power supply using the
appropriate lugs at the wiring end, or with no lugs, as illustrated. The proper wiring sequence is
ground to ground, positive to positive, and negative to negative. Note that the ground wire should
always be connected first and disconnected last.
Statement 197

Figure 3-15

DC Power Supply Connections

On/off
switch

LEDs

31628

Terminal
block

Mounting screw

Mounting screw

Mounting

screw

IN OK

DC OK

OTF

IN OK

DC OK

OTF

LEDs

Terminal
block

Strain-relief

clamps

Strain-relief

clamps