4) Systems containing oxygen – Many hydronic systems contain enough dissolved oxygen to cause

severe corrosion damage to a cast iron boiler such as the ODV. Some examples include:

• Radiant systems that employ tubing without an oxygen barrier.

• Systems with routine additions of fresh water

• Systems which are open to the atmosphere

If the boiler is to be used in such a system, it must be separated from the oxygenated water being

heated with a heat exchanger as shown in Figure 20. Consult the heat exchanger manufacturer

for proper heat exchanger sizing as well as flow and temperature requirements. All components

on the oxygenated side of the heat exchanger, such as the pump and expansion tank, must be

designed for use in oxygenated water.