VII Fuel Piping

Two basic piping systems are used to connect the boiler to the oil supply:

1) One-Pipe – Recommended where the fuel pump is below the lowest possible level of the oil in

the tank. Basic piping is shown in Figure 21a.

2) Two-Pipe – Recommended where the fuel pump is above the lowest possible level of the oil in

the tank. This system is self-priming. Basic piping is shown in Figure 21b.

Consult the instructions supplied with the pump for limitations on lift, horizontal run, and required line

sizes. Pumps supplied with the ODV boiler generally require the installation of a bypass plug when

converted for use in a two-pipe system. See the pump instructions for specific information. Also note the

following:

1) If the boiler is being installed as a replacement, the existing oil system may be two-pipe even

though the pump is below the lowest level in the oil tank. Such systems should be converted

to one-pipe systems as doing so will result in warmer oil temperatures, lower vacuums, and

longer filter life.

IMPORTANT

• Installation of oil storage tanks, fill pipes, and oil lines must conform to local code

requirements. In the absence of any codes, installation must be in conformance

with ANSI/NFPA-31.

• Use of this boiler with an unenclosed above ground outdoor oil tank is not

recommended.