Crown Boiler ODV-125 User Manual

Page 7

Advertising
background image

4

V Vent System Installation

The ODV boiler is shipped with a complete venting system consisting of the following components:

• FDVS-4 direct vent terminal

• Backing plate

• 15-ft length of insulated 4” FOVP flexible oil vent pipe

• 4” x 7” appliance adapter

• (2) Cover rings

• (2) Cover sleeves

• Bagged hardware

• (4) Inner pipe clamps

• 20 ft length 4” flexible aluminum air intake pipe

• (2) Hose clamps

• “Red” high temperature RTV silicone sealant

1) LOCATING THE TERMINAL – Observe the following requirements in locating the terminal:

a) Maximum wall thickness through which terminal can be installed is 12”.

b) Wall can be combustible or noncombustible.

c) Bottom of terminal must be at least 12 inches above the normal snowline. If normal snowfall is

negligible, terminal must be at least 12 inches above grade (Fig 2).

d) Bottom of Terminal must be at least 7 feet above a public walkway (Fig 2).

e) Locate edge of terminal at least 4 ft horizontally from doors, windows, or gravity air inlets. Do

not put terminal under windows which can be opened (Fig 2).

f) Terminal must be close enough to boiler to be connected to it using the vent components

supplied.

CAUTION

• Do not use vent system components other than those supplied with the boiler

• Use only the red RTV sealant provided with this boiler anywhere that this manual

calls for the use of “sealant”

• Combustion air must be brought from outside as shown in this manual

• Do not install a “vacuum relief” damper

• Do not attempt to splice vent piping

• Do not put holes in venting

WARNING

• Read the installation instructions carefully and completely before proceeding

with the installation of vent system.

• For continued safe operation, the appliance vent system must be inspected and

maintained annually by a qualified agency.

Failure to properly maintain the appliance vent system combination can lead to

Death, Personal Injury and or Property Damage.

• Plan the vent system layout before installation to avoid the possibility of

accidental contact with concealed wiring or plumbing inside walls.