2) Do not use compression fittings in oil piping.

3) Do not use Teflon tape in oil piping

4) Do not manifold multiple oil appliances on a two-pipe system. Run dedicated lines for each

appliance back to the tank or use a transfer pump and day tank to get oil to a location where it

can be gravity fed to each appliance.

5) Do not use check valves in gravity feed systems.

6) Where a new oil tank is to be installed, and where codes permit, the best location for the tank is

in a warm space (such as basement) where a one-pipe gravity system can be used. Such a

location will eliminate problems caused by air-infiltration and cold oil.

7) Use only #2 fuel oil with physical and chemical characteristics meeting the requirements in

ASTM D-396.

VIII WIRING

Figure 22 is a connections diagram for the ODV boiler. The following connections must be made in

the field:

L1 – Line voltage “hot”

L2 – Line voltage “neutral

C1 – Circulator “hot”

C2 – Circulator “neutral”

T, T – 24 volt thermostat connections.

Green Screw in L7248A – Ground connection

This boiler must be wired to a dedicated circuit having a 15-amp fuse or circuit breaker. The minimum

size wire that should be used in this circuit is 14 AWG.

If this boiler is to be used in a multiple zone installation, T, T are generally connected to either zone

valve end switches or a set of dry relay contacts which will start the boiler when any one zone calls for

heat. A separate transformer must be used to power zone valves. If this boiler is to be used in a circulator

zone system, terminals C1 and C2 cannot be used as they will be energized regardless of which zone is

calling for heat.

CAUTION

Fuel oil will attack silicone pressure switch tubing. If at all possible, route oil lines

under air inlet collar.

WARNING

All wiring and grounding must be done in accordance with the authority having ju-

risdiction or, in the absence of such requirements, with the National Electrical Code

(ANSI/NFPA 70).