2) If a zero smoke cannot be obtained at a CO2 between 11.0 and 12.5%, check the following:

a) Check nozzle and settings against those shown in Table 2 below. Nozzle must be identical

to that called for in Table 2 including manufacturer. Check the burner manufacturer’s manual

for dimensional settings not shown in this manual (e.g. electrode settings, nozzle to spinner

dimensions, etc).

b) Check oil lines for air infiltration.

c) Inspect burner air handling components (burner head, spinner etc.) for visible damage or

distortion.

d) Check that oil characteristics are in conformance with ASTM D 396.

e) Check for oil leaks in the nozzle line and pump seal.

f) Nozzle may be defective or partially plugged – replace with an identical nozzle.

g) Check the vacuum at the inlet to the fuel pump to be certain that it is not in excess of the

pump manufacturer’s specifications.

ODV-75

ODV-100

ODV-125

CARLIN BURNER

EZ1-HPV

EZ1-HPV

EZ1-HPV

CARLIN PRIMARY CONTROL #

6020002

6020002

6020002

PRE/POST PURGE TIMING (s)

30/120

30/120

30/120

INSERTION LENGTH

2 1/4

2 1/4

2 1/4

PITCH ANGLE (degrees)

2

2

2

NOZZLE

DELAVAN DELAVAN DELAVAN

0.65/70W

0.85/60A

1.00/60A

PUMP PRESS (psi)

150

150

150

HEAD BAR

0.75

0.85 - 1.00 1.10 - 1.25

STARTING SHUTTER SETTING

0.75

1.00

1.25

MAX. SMOKE (Bacharach scale)

TRACE

TRACE

TRACE

CO2:

MIN.

11.0

11.0

11.0

MAX.

12.5

12.5

12.5

TABLE 2

ODV BURNER APPLICATIONS