20

6) Start the boiler. Immediately take a smoke. If any smoke is present, open the air adjustment to

obtain a zero smoke.

7) Allow boiler to warm up for about 15 minutes or until the binder has completely burned out of

the combustion chamber. Adjust the air to obtain a CO2 between 11.0% and 12.5% with a zero

smoke. If a zero smoke cannot be obtained in this range of CO2s, see “Service Notes” on

page 18.

8) Cycle the boiler several times to make sure that the light-offs are smooth and reliable.

9) Allow the boiler to fire until the water temperature reaches the high limit setting. Confirm that

the high limit shuts down the burner.

10) Confirm that the thermostat/s cycle the burner and the appropriate circulator/s and/or zone

valves.

11) Recheck the piping for leaks. Repair any leaks found at once.

12) Inspect the vent system for flue gas leaks. Repair any leaks found before leaving the boiler in

operation.

X Service Notes

1) The pressure switch on the ODV is designed to protect the boiler against blockages in the vent

or intake piping. The electrical contacts on this switch are connected to “T-T” on the burner’s

primary control and are normally closed. This pressure switch is equipped with an orifice on the

negative pressure side of so that the blockage must be present for several seconds before the

switch shuts down the burner.

In the event that a blockage appears in either side of the vent/ intake piping, the pressure switch

will open the burner after a delay of 10 –60seconds. The burner will go into post purge and

then shut down. After a delay of approximately 4 seconds it will go into pre-purge. If the block-

age is still present, the burner will cycle in and out of pre-purge at intervals of approximately 20

seconds until the blockage is removed or power to the burner is interrupted.

Each size ODV boiler has a different pressure switch setting:

Model

Switch Contacts Open on Pressure Rise

ODV-75

0.23 +/- 0.025” w.c.

ODV-100

0.305 +/- 0.025” w.c.

ODV-125

0.45 +/- 0.025 “ w.c.

Route the 1/8 silicone tubing shipped wrapped over the intake collar along the left side of the

jacket to the hose barb on the 7 x 4 adapter. Use the cable clamps provided to attach this hose to

the left side jacket panel. Figure 23 shows the pressure switch tubing connections.

NOTE

The ODV boiler is equipped with a ceramic combustion chamber. On initial start-up,

the binder on this chamber will burn out, possibly resulting in a yellow spot on smoke

paper. This binder should burn out in approximately 30 minutes of operation and

should not reappear. Successive smoke readings taken over this 30-minute “burn-out”

period should result in decreasing amounts of yellow on each smoke spot.