Flintec PC6D User Manual

Page 32

Advertising
background image

Page Manual PC6D CANopen

32

Mode 1 Characteristic (FIR-Filter)

FL

Settling time

to 0.1%

(ms)

3 dB Cut-off

(Hz)

20 dB

damping at

frequency

(Hz)

40 dB

damping at

frequency

(Hz)

Damping in

the

stopband

(dB)

Stopband

(Hz)

Output rate

max.

(samples/s)

0 no

filtering **

1200

1 47

19.7 48 64

>90

>80

1200

2 93

9.8 24 32

>90

>40

600

3 140

6.5 16 21 >90

>26

400

4 187

4.9 12 16 >90

>20

300

5 233

3.9 10 13 >90

>16

240

6 280

3.2

8 11 >90

>13

200

7 327

2.8

7 9 >90

>11

172

8 373

2.5

6 8 >90

>10

150

* * Antialiasing filter 17 Hz @ 60 dB/decade

Attention: In mode 1 the output rate is dependant on the selected filter level (FL) and will be
automatically adjusted by the PC6D.

UR

Set the update rate (average building)

[ 2100sub11 ]

This command will define over how many measurements, from the preceeding IIR or FIR
filter, an average will be calculated. The average will be calculated over 2

UR

samples.

Permitted values 0...7 (see table below).

UR

0

1

2

3

4

5

6

7

No. of samples

1

2

4

8

16

32

64

128

Check / adjustment update rate:

Master (PC / PLC) sends

Device responds

Result

UR U+0001

Request: average over 2 samples

UR_4 OK

Setting: average over 16 samples

Factory default: 0 [no average, = 1200 samples/s]

Remark to Mode 1

Dependency Output Rate - averaging UR - Filter FL

UR

Output Rate samples/s

FL0

FL1

19.7 Hz

FL2

9.8 Hz

FL3

6.5 Hz

FL4

4.9 Hz

FL5

3.9 Hz

FL6

3.2 Hz

FL7

2.8 Hz

FL8

2.5 Hz

0

1200

1200 600 400 300 240 200 172 150

1

600 600 300 200 150 120 100 85.7 75

2

300 300 150 100 75 60 50 43 37.5

3

150 150 75 50 37.5 30 25 21.4 18.7

4 75 75 37.5 25 18.7 15 12.5 10.7 9.4

5 37.5 37.5 18.7 12.5 9.4 7.5 6.26 5.36 4.68

6

18.7 18.7 9.4 6.26 4.68 3.76 3.12 2.68 2.34

7 9.4 9.4 4.68 3.12 2.34 1.88 1.56 1.34 1.18