5.10

Trigger Special Commands– RW, TT, TS, DT, TW, TI, HT

Remark: These commands are

only available in firmware 102.183.v.1.10.

Note: All setups should be stored with the WP command before power off.

RW

Re-Trigger Window

[ 2500sub03 ]

Set the re-trigger window in counts (digits) without decimal point.

If the weight relative to the

current average value changes by more than the RW value the average cycle will be
restarted using TT as measure time.To automatically issue the re-trigger command, the time
period over which an increase of weight average is measured has to be defined by using the
command DT.

Permitted values are 0 …65535 counts.

Master (PC / PLC) sends

Device responds

Result

RW R+65535

Request: RW=65535

RW_500 OK

Setting: RW=500d

Factory default: 65535

TT

Re-Trigger Time

[2500sub04 ]

Set the re-trigger time in milliseconds [ms].

Re-trigger time is the average time used by the re-

trigger function. If set to zero the re-trigger function is disabled.

Permitted values are 0 …65535 ms.

Master (PC / PLC) sends

Device responds

Result

TT T+65535

Request: TT=65535

TT_300 OK

Setting: TT=300ms

Factory default: 65535

TS

Re-Trigger Stop

[ 2500sub08 ]

Set the re-trigger stop in counts (digits) without decimal point.

In case of a (TS) decrease in

weight relative to the current average value the re-trigger function is stopped.

Permitted values are 0 …65535 counts.

Master (PC / PLC) sends

Device responds

Result

TS T+00000

Request: TS=00000

TS_480 OK

Setting: TT=480d

Factory default: 00000

[ The Re-Trigger function can also be stopped by sending 01 instead of 80 with
RPDO2 [00 01]. ]