Panel location, Power and wire length – Interlogix Concord 4 REV C Installation Manual User Manual

Page 2

Advertising
background image

2

Concord 4 Installation Guide

Phone line
connection

Allow s panel to communicate w ith central
monitoring station and/or pagers.

Note:

The total current sourced from all terminals cannot

exceed 1 amp.

Panel location

Before permanently mounting the panel, use the
following guidelines to choose a mounting location.

To help reduce wire run lengths and labor, centrally locate

the panel with relation to detection devices whenever

possible.

Locate the panel where the temperature will not exceed

120ºF (49ºC) or fall below 32ºF (0ºC).

To prevent wire runs from picking up electrical noise,

avoid running wires parallel with electrical wiring or fixtures

such as fluorescent lighting.

Mount the panel at a comfortable working height.

Leave at least 24 inches in front of the panel to open the

cabinet door and access the panel.

Leave space to the left and right of the panel for wiring,

phone jack, and mounting optional modules.

Leave at least 9 inches above the panel cabinet for

antennas.

Power and wire length

The panel can supply up to 1 amp (1,000 mA) in full load
alarm condition for system devices connected to panel
terminals 4 (+12V), 7 and 8 (speaker terminals), 9
(OUT1), 11 (+12V), 24 (2W SMK ZONE 8), and

SnapCard terminals.

For 24-hour backup, the total standby current draw for all
devices connected to panel terminals 4 (+12V), 9
(OUT1), 11 (+12V), 24 (if configured for two-wire smoke
loop), and SnapCard terminals is limited to 90 mA
(during normal standby condition) using a 4.5 or 5.0 Ah
battery, or 190 mA (during normal standby condition)
using a 7.0 Ah battery.

The total system wire length allowed can vary depending

on devices powered by the panel, the wire length
between devices and the pane, and the combined wire
length of all devices.

Table 3 below describes the maximum wire length
allowed between compatible devices and the panel, and
the minimum and maximum current draw of each device.

Table 3: Wire length requirements

Device

Max. w ire
length to
panel

Standby
m A draw

Alarm m A
draw

SuperBus 2000 2x16 LCD
alphanumeric touchpad

22 ga.: 300 ft.
18 ga.: 750 ft.

15 mA

90 mA

SuperBus 2000 ATP 1000
alphanumeric touchpad

22 ga.: 300 ft.
18 ga.: 750 ft.

12 mA

110 mA

SuperBus 2000 ATP 2100
alphanumeric touchpad

22 ga.: 300 ft.
18 ga.: 750 ft.

30 mA

165 mA

SuperBus 2000 ATP 2600
alphanumeric touchpad

22 ga.: 300 ft.
18 ga.: 750 ft.

30 mA

165 mA

SuperBus 2000 GTS 50

22 ga.: 100 ft.
18 ga.: 250 ft.

270 mA

300 mA

SuperBus 2000 fixed display
touchpad

22 ga.: 300 ft.
18 ga.: 700 ft.

11 mA

65 mA

SuperBus 2000 FTP 1000
fixed display touchpad

22 ga.: 300 ft.
18 ga.: 700 ft.

12 mA

75 mA

SuperBus 2000 RF
transceiver

22 ga.: 1,000 ft.
18 ga.: 2,500 ft.

45 mA

55 mA

SuperBus 2000 RF receiver

1

22 ga.: 1,100 ft.
18 ga.: 2,800 ft.

35 mA

35 mA

SuperBus 2000 phone
interface/voice module

22 ga.: 40 ft.
18 ga.: 120 ft.

25 mA

600 mA

SuperBus 2000 voice-only
module

22 ga.: 40 ft.
18 ga.: 120 ft.

20 mA

300 mA
(jumper)
600 mA (no
jumper)

SuperBus 2000 2 amp
pow er supply

N/A

No load

No load

4 input/2 output SnapCard

N/A

20 mA

185 mA

1

8Z hardw ired zone
expander SnapCard

N/A

38 mA

230 mA

1

4 output SnapCard

N/A

1 mA

130 mA

1

SuperBus 2000 8Z input
module

22 ga.: 1,800 ft.
18 ga.: 4,000 ft.

18 mA

35 mA

SuperBus 2000 4-relay
output module

22 ga.: 350 ft.
18 ga.: 900 ft.

12 mA

180 mA

SuperBus 2000 energy
saver module

22 ga.: 1,600 ft.
18 ga.: 4,000 ft.

20 mA

20 mA

SuperBus 2000 cellular
backup module

Standard
pow er 22 ga.:
15 ft. 18 ga.:
40 ft. High
pow er 22
ga.: 10 ft. 18
ga.: 30 ft.

90 mA

90 mA

1600 mA

1900 mA

SuperBus 2000 automation
module

22 ga.: 1,500 ft.
18 ga.: 4,000 ft.

30 mA

35 mA

SuperBus 2000 w ireless
gatew ay-ready kit

22 ga.: 40 ft.
18 ga.: 90 ft.

65 mA

1600 mA

Interrogator 200

22 ga.: 3,200 ft.
18 ga.: 4,500 ft.

10 mA

10 mA