NX-8 Control

25

LOCATION 44 - DURESS CODE (6 segments, numerical data)

Location 44 contains the "Duress" code. This Location contains either 4 or 6 digits. If the 6-digit code option is
enabled in Location 41, THIS CODE MUST CONTAIN SIX (6) DIGITS. If the 6-digit option is not enabled in location
41, the last 2 digits will be ignored. If the duress code is programmed, it will work for all partitions.

LOCATION 45 - AUXILIARY OUTPUT 1-4 PARTITION SELECTION (4 segments, feature selection data)
Location 45 is used to select which partition(s) the events must occur in before the output will activate. Location 45
has 4 segments. Segment 1 corresponds to output 1, and Segment 4 corresponds to output 4.


Segment 1

Segment 2

Segment 3

Segment 4

(Auxiliary 1)

(Auxiliary 2)

(Auxiliary 3)

(Auxiliary 4)

1= Partition #1

1= Partition #1

1= Partition #1

1= Partition #1

2= Partition #2

2= Partition #2

2= Partition #2

2= Partition #2

3= Partition #3

3= Partition #3

3= Partition #3

3= Partition #3

4= Partition #4

4= Partition #4

4= Partition #4

4= Partition #4

5= Partition #5

5= Partition #5

5= Partition #5

5= Partition #5

6= Partition #6

6= Partition #6

6= Partition #6

6= Partition #6

7= Partition #7

7= Partition #7

7= Partition #7

7= Partition #7

8= Partition #8

8= Partition #8

8= Partition #8

8= Partition #8

LOCATION 46 - AUXILIARY OUTPUT 1-4 SPECIAL TIMING (4 segments, feature selection data)
Location 46 contains special timing feature activation for the four auxiliary outputs. Segment 1 corresponds to output
1, Segment 4 corresponds to output 4.


Segments 1 - 4:

1 = On if output should be timed in minutes; Off if timed in seconds.
2 = On if output should latch; Off if output should be timed.

3 = On if output should stop timing upon code entry; Off if the output should continue to time

upon code entry.

4 = On if output should only activate between the closing and opening time in loc. 52 and 53.
5 = On if output should only activate between the opening and closing time in loc. 52 and 53.
6 = On if output should be inverted (0 volts going to 12 volts when activated).
7 = Reserved.
8 = Reserved.

LOCATION 47 - AUXILIARY OUTPUT #1, EVENT AND TIME (2 segments, numerical data)


Segment 1:
Use

Table 1 on page 26 to select the event that will activate Auxiliary Output 1.

Segment 2: Program the timing from 0-255 (minutes or seconds, depending on data programmed in

Segment 1, Location 46). Programming a "0" makes the output follow the event.

LOCATION 48 - AUXILIARY OUTPUT #2, EVENT AND TIME (2 segments, numerical data)


Segment 1:
Use

Table 1 on page 26 to select the event that will activate Auxiliary Output 2.

Segment 2: Program the timing from 0-255 (minutes or seconds, depending on data programmed in

Segment 2, Location 46). Programming a "0" makes the output follow the event.

LOCATION 49- AUXILIARY OUTPUT #3, EVENT AND TIME (2 segments, numerical data)


Segment 1:
Use

Table 1 on page 26 to select the event that will activate Auxiliary Output 3.

Segment 2: Program the timing from 0-255 (minutes or seconds, depending on data programmed in

Segment 3, Location 46). Programming a "0" makes the output follow the event.

LOCATION 50- AUXILIARY OUTPUT #4, EVENT AND TIME (2 segments, numerical data)


Segment 1:
Use

Table 1 on page 26 to select the event that will activate Auxiliary Output 4. .

Segment 2: Program the timing from 0-255 (minutes or seconds, depending on data programmed in

Segment 4, Location 46). Programming a "0" makes the output follow the event.