Ansi / sia cp-01 requirements, Cp-01 feature, Description – Interlogix NX-8 User Manual

Page 60: Feature description, As shown in manual, Program, Seg / opt, Factory, Default, Cp-01 required

Advertising
background image

NX-8 Control

60

ANSI / SIA CP-01 REQUIREMENTS

IMPORTANT NOTE: UL requirements take priority over SIA requirements.

To meet SIA CP-01 requirements –

Minimum System Requirements: 1 control panel; 2 keypads (or 1 keypad per partition for multi-partitioned systems)

Remote arming shall NOT be enabled in SIA classified installations.

Off-premise transmission must be in the SIA format.

The Abort window and Entry Delay must not exceed 1 minute.

CAUTION – A call waiting cancel on a non-call waiting line will prevent successful connection to the central station.

CP-01 Feature

Description

Feature Description

as shown in manual

Program

Loc

Seg / Opt

Factory

Default

CP-01 Required

Setting

Exit Time

Exit 1 Delay

24

2

60

45 – 240 sec.

Exit 2 Delay

24

4

60

45 – 240 sec.

Progress Annuncation / Disable
– for Silent Exit

Silent Keypad Option

9 3

2

All annunciators enabled

Allowed
(individual keypads may be disabled)

Exit Time Restart

This feature is non-programmable in the panel.

Enabled

Auto Stay Arm on Unvacated Premises

Auto Bypass

23

1 / 3

Enabled Enabled

Exit Time and Progress
Annunciation / Disable
– for Remote Arm

This feature is non-programmable in the panel. -- Exit time and progress are always enabled.

Enabled (may be disabled for remote arming)

Entry Delay(s)

Entry 1 Delay

24

1

30

30 – 240 sec.

Entry

2

Delay

24

3

30

30 – 240 sec.

Abort Window
– for Non-Fire Zones

Dialer Delay

40

8

30 Enabled

(may be disabled by zone/ zone type)

Abort Window Time
– for Non-Fire Zones

Dialer Delay

40

8

30

15 – 45 sec.

NOTE:
Combined
Abort window
and Entry
Delay must
not exceed 1
minute.

Abort Annunciation

This feature is non-programmable in the panel. -- Flashing Cancel LED goes off when disarming.

Enabled

Cancel Annunciation

Cancel

23

3 / 6

Enabled Enabled

Duress Feature

Duress

44

Disabled

Disabled

Cross Zoning

2 Trips on Cross Zone

37

5 / 4

Disabled

Required

Keypad sounds on Cross Zone trip

39

5

Disabled

Zone Type Characteristic

111

3 / 4

Disabled

Programmable Cross Zoning Time

Cross Zone Time

40

6

5 minutes

Allowed

Swinger Shutdown

Swinger Shutdown Count

38

n/a

Enabled for 1 trip

For all non-fire zones, shut down at 1–2 trips

Swinger Shutdown Disable

Swinger Shutdown Count

38

n/a

Enabled for 1 trip

Allowed

Fire Alarm Verification

Fire Alarm Verification Time

40

9

Disabled Required

(depends on panel & sensors)

Call Waiting Cancel

Must be programmed as part of the

phone number

0

n/a

n/a

Required (depends on user phone line)

Default Changes (from prior versions):

Recent Closing

23

3 / 7

Enabled

Exit Error

23

3 / 8

Enabled

Power

Up

Delay

40

3

60 sec.


Advertising