Carrier RTU OPEN 11-808-427-01 User Manual

Page 16

Advertising
background image

Installation

10

RTU Open

1

Turn off the RTU Open's power. The controller reads the address each time you apply power to it.

2

Using the rotary switches, set the MSB (SW1) (10's) switch to the tens digit of the address, and set the

LSB (SW2)

(1's) switch to the ones digit.

EXAMPLE

To set the RTU Open’s address to 01, point the arrow on the MSB (SW1) switch to 0 and the

arrow on the LSB (SW2) switch to 1.

3

Turn on the RTU Open's power.

CAUTION

The factory default setting is 00 and must be changed to successfully install your RTU Open.


To set the RTU Open's communications protocol and baud rate

RTU Open's SW3 DIP switches are used to set the controller's protocol and baud rate. The protocol and speed

selection is determined by the network on which the controller will be installed. For Carrier BACnet

implementations, select MS/TP @ 76.8 k as follows:

1

Power down the RTU Open. The controller reads the protocol and baud rate each time you apply power to

it.

2

Set SW3 DIP switches 1, 2, and 4 to On to configure the controller for BACnet MS/TP and 76.8 k baud.

3

Power up the RTU Open.

NOTE

Other protocols and baud rates are available. See the RTU Open Integration Guide for additional

instructions.