Wiring a status switch, Wiring specifications, E 32) – Carrier RTU OPEN 11-808-427-01 User Manual

Page 38

Advertising
background image

Installation

32

RTU Open

To wire an enthalpy switch (differential) to the controller

Wiring diagram for optional enthalpy sensor mounted in the return air for differential enthalpy:

Wiring a status switch

Filter - Part #CRSTATUS005A00 or field-supplied
Fan status - Part #CRSTATUS005A00 or field-supplied

Filter and/or fan status switches may be installed to provide a Dirty Filter indication or Fan Running status.

Wiring specifications

Cable from sensor to controller:

If <100 ft (30.5 meters) 22 AWG, unshielded

If >100 ft (30.5 meters) 22 AWG, shielded

Maximum length:

500 feet (152 meters)