Wiring an spt sensor, Rnet wiring specifications, E 20) – Carrier RTU OPEN 11-808-427-01 User Manual

Page 26

Advertising
background image

Installation

20

RTU Open

Wiring an SPT sensor

The RTU Open is connected to a wall-mounted space temperature sensor to monitor room temperature.
An i-Vu® Open Control System offers the following SPT sensors:

Sensor

Part #

Features

SPT Standard

SPS

•

Local access port

•

No operator control

SPT Plus

SPPL

•

Slide potentiometer to adjust setpoint

•

MANUAL ON button to override schedule

•

LED to show occupied status

•

Local access port

SPT Pro

SPP

•

LCD display

•

MANUAL ON button to override schedule

•

WARMER and COOLER buttons to adjust setpoint

•

INFO button to cycle through zone and outside air temperatures,

setpoints, and local override time

•

Local access port


You wire SPT sensors to the RTU Open's Rnet port. An Rnet can consist of any of the following combinations

of devices wired in a daisy-chain configuration:
•

1 SPT Plus or SPT Pro

•

1–4 SPT Standards

•

1–4 SPT Standards, and 1 SPT Plus or SPT Pro

•

Any of the above combinations, plus up to 2 BACview

6

devices, but no more than 6 devices total

NOTES
•

If you have 2 BACview

6

devices, the second BACview

6

device must have a separate power supply with the

same ground as the controller.

•

If the Rnet has multiple SPT Standard sensors, you must give each a unique address on the Rnet. See

the Carrier Sensors Installation Guide.

•

If the Rnet has multiple BACview devices, you must give each a unique address on the Rnet. See the

BACview Installation and User Guide.



Rnet wiring specifications

NOTE

Use the specified type of wire and cable for maximum signal integrity.

Description

4 conductor, unshielded, CMP, plenum rated cable

Conductor

18 AWG

Maximum length

500 feet (152 meters)

Recommended coloring

Jacket: White

Wiring: Black, white, green, red

UL temperature rating

32–167°F (0–75°C)