Service configuration properties, E 41) – Carrier RTU OPEN 11-808-427-01 User Manual

Page 47

Advertising
background image

RTU Open

41

Point Name/Description

Default/Range

Optimal Start

– The number of hours prior to occupancy, at which the Optimal Start function

may begin to adjust the effective setpoints to achieve the occupied setpoints by the time

scheduled occupancy begins. Enter 0 to disable Optimal Start.

D:
R:

4 hr
0 to 4 hr

Occ Relative Humidity Setpoint

– The percentage of relative humidity in the space during

occupancy that will energize BO - 6 (Humidi-MiZer™).

D:
R:

60%rh
0 to Unoccupied

RH Control

Setpoint

Unocc Relative Humidity Setpoint

– The percentage of relative humidity in the space during

the unoccupied time period that starts the unit and energizes BO - 6 (Humidi-MiZer™).

D:
R:

95%
30 to 100%

DCV Max Ctrl Setpoint

– The design difference between indoor and outdoor CO2 levels.

D:
R:

650ppm
0 to 9999 ppm

Power Exhaust Setpoint

- The outside air damper position at which the controller energizes

the Power Exhaust relay. Configuration >Service Configuration > Economizer Exists must be

set to Yes, and Configuration >Service Configuration > Continuous Occupied Exhaust must

be set to No.

D:
R:

50% Open
20 to 90% Open


Service Configuration properties

Navigation:

i-Vu / Field Assistant:
BACview:

Properties

>

Equipment

>

Configuration

>

Service Configuration

HOME > CONFIG > SERVICE

Point Name/Description

Default/Range

Unit Type

– The type of equipment that the RTU Open is controlling.

Options:

Heat/Cool

– Standard rooftop air handling unit.

HP O/B Ctrl

– Heat Pump application, uses reversing valve output to control heating and

cooling.

HP Y1/W1 Ctrl

– Carrier Heat Pump application only.

D:
R:

Heat/Cool
Heat/Cool

HP O/B Ctrl

HP Y1/W1 Ctrl

Compressor Stages

– The number of mechanical cooling stages.

D:
R:

One Stage
One Stage

Two Stages

Economizer Exists

– Set to Yes to enable economizer control for units equipped with an

economizer damper.

D:
R:

No
No/Yes

Reversing Valve Output

– Set to O = Reversing Valve output on with cooling. Set to B =

Reversing Valve

output on with heating.

D:
R:

O
O / B

Heat Type

– The type of heating that the unit has.

D:
R:

Electric
Electric/Gas

Number Of Heat Stages

– The number of heat stages.

D:
R:

2

1 /2 /0 (no heating)