Start-up
42
RTU Open
Point Name/Description
Default/Range
Continuous Occupied Exhaust
– Configures the exhaust fan control strategy (BO-8). If Yes,
the power exhaust runs continuously in occupied mode and is off in unoccupied mode. If
No
, the power exhaust is controlled by the Power Exhaust Setpoint.
D:
R:
No
No/Yes
Indoor CO2 Sensor Value @min (ma)
– The CO2 value that corresponds to a 4mA input at
the appropriate input channel.
D:
R:
0 ppm
0 to 9999 ppm
Indoor CO2 Sensor Value @max (ma)
– The CO2 value that corresponds to a 20mA input at
the appropriate input channel.
D:
R:
2000 ppm
0 to 9999 ppm
Outdoor CO2 Sensor Value @min (ma)
– The CO2 value that corresponds to a 4 mA input
at the appropriate input channel.
D:
R:
0 ppm
0 to 9999 ppm
Outdoor CO2 Sensor Value @max (ma)
– The CO2 value that corresponds to a 20 mA input
at the appropriate input channel.
D:
R:
2000 ppm
0 to 9999 ppm