Sequence of operation, Occupancy – Carrier RTU OPEN 11-808-427-01 User Manual

Page 49

Advertising
background image

RTU Open

43

The RTU Open supports various types of constant volume air source configurations:
•

Standard heat/cool unit types with up to 2-stages of mechanical cooling and gas or electric heating

•

Heat pump units utilizing a reversing valve output for heating and cooling control

•

Heat pump unit (Carrier) with an OEM control board

•

Economizer, CO2, Demand Limiting, and RH control strategies are available for appropriately equipped

units


The RTU Open may operate as part of a linked VVT system or as a stand-alone controller.

Occupancy

The RTU Open’s operation depends upon its occupancy state (Occupied/Unoccupied). The RTU Open

operates continuously in the Occupied mode until you configure an occupancy schedule.
An occupancy schedule may be:
•

A local schedule configured in the controller using a BACview device or Field Assistant

•

A BACnet schedule configured in the i-Vu application, networked through an i-Vu Open Router

•

A BACnet or local schedule configured for subordinate VVT Zones, networked through an i-Vu Open

Router(s) and employing Linkage

To set up occupancy schedules, consult the documentation for your user interface.
NOTE

A BACnet schedule, downloaded from the i-Vu application will overwrite a local schedule that was set

up with a BACview device or Field Assistant.
Occupancy Source

- the following settings determine occupancy. See Unit configuration (page 60).

Options:
•

Always Occupied

– Controller operates continuously, regardless of any configured schedule

•

BAS On/Off

– Occupancy is set over the network by another device or a third party BAS. Refer to the RTU

Open Integration Guide for additional instructions in communication protocols.

•

Remote Occ Input

– Controller monitors an input contact connected to one of the available binary inputs

configured to receive it. You must set Unit Configuration > Occupancy Source to Remote Occ Input and

one Input Switch Configuration to Remote Occupancy.





Sequence of Operation