Control unit is in “standby” mode (continued) – LAARS NeoTherm NTV (Sizes 150–285 MBTU/h) - Service Manual User Manual

Page 16

Advertising
background image

6

Service Manual NeoTherm 80 - NeoTherm 285

A4

cont.

Control Unit is in “Standby” Mode (continued)

Example:

High flue temperature trips

High Stack Temp. Sensor.

Unit will not run for 20 min.,

then automatically resets.

Controller reacting

to a temporary problem?

No

Units with original (white) user interface -

See Section A5

“Changing Control Settings,

Change Not Complete”

Were you changing

the control settings?

Yes

No

See Section B3

“Checking the Safety Interlocks”

Problem with

safety interlock

circuit?