Using the current user interface - continued – LAARS NeoTherm NTV (Sizes 150–285 MBTU/h) - Service Manual User Manual

Page 83

Advertising
background image

73

Service Manual NeoTherm 80 - NeoTherm 285

You will notice that the system did not ask you for a

password, so this is one of the values that can be

changed by anyone.

Entering a Time
The controller uses several different timing functions,

and you can change some of these. (In the example

shown in Fig. D5-5, we will use the screen for the Anti

Short-Cycle Time.
• The current setting appears in the upper right-hand

corner of the screen. In this example, this is 1 min-

ute.

• The numbers near the left edge of the screen show

the allowable range for this value. In this case, the

time can be set anywhere between 1 minute and 15

minutes.

In this example we will change the time delay to 5 min-

utes.
• Press the Left- and Right-Arrow buttons to move to

the box you want. In this case, we want to change

the middle box - the box for Minutes.

• Use the Up- and Down-Arrow buttons to change the

value in that box.

• You can change the numbers in the other boxes in

the same way.

• When the new setting is correct, press the round OK

button.

Fig. D5-5 - Changing a timing function

Using the Current User Interface - continued

D5

cont.

Advertising