App1, Appendix 1 - error codes (continued), Cont – LAARS NeoTherm NTV (Sizes 150–285 MBTU/h) - Service Manual User Manual

Page 92

Advertising
background image

82

Service Manual NeoTherm 80 - NeoTherm 285

Appendix 1 - Error Codes (continued)

App1

cont.

Code Description

L or H Procedure

11

Internal fault:
Invalid burner control state flag

L

Internal fault
1. Reset module
2. If fault repeats, replace module.

12

Internal fault:
Safety relay drive cap short

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

13

Internal fault:
PII (Pre-Ignition Interlock) shorted to ILK

(Interlock)

H or L Internal fault

1. Reset module
2. If fault repeats, replace module.

15

Internal fault:
Safety relay test failed due to feedback on

L

Internal fault
1. Reset module
2. If fault repeats, replace module.

16

Internal fault:
Safety relay test failed due to safety relay off

L

Internal fault
1. Reset module
2. If fault repeats, replace module.

17

Internal fault:
Safety relay test failed due to safety relay

not off

L

Internal fault
1. Reset module
2. If fault repeats, replace module.

18

Internal fault:
Safety relay test failed due to feedback not

on

L

Internal fault
1. Reset module
2. If fault repeats, replace module.

19

Internal fault:
Safety RAM write

L

Internal fault
1. Reset module
2. If fault repeats, replace module.

20

Internal fault:
Flame ripple and overflow

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

21

Internal fault:
Flame number of sample mismatch

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

22

Internal fault:
Flame bias out of range

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

23

Internal fault:
Bias changed since heating cycle starts

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

24

Internal fault:
Spark voltage stuck low or high

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

25

Internal fault:
Spark voltage changed too much during

flame sensing time

H

Internal fault
1. Reset module
2. If fault repeats, replace module.

Advertising
This manual is related to the following products: